Products
RIP/RIF Oil-Air Transformer Bushing
FBRG / FBRGL / EBRG / EBRGL Series | 12kV - 550kV | 630A - 5000A
Application
Technical drawing — dimensions and interfaces can be customized to your transformer flange.
Main Technical Index
| Main Technical Index (per IEC 60137 / GB/T 4109 / Q/ZL-JS-501-2026) | |||||||
|---|---|---|---|---|---|---|---|
| Rated Equipment Voltage Um (kV) | 24 | 40.5 | 72.5 | 126 | 252 | 363 | 550 |
| Power Frequency Withstand, 1 min (kV) | 61 | 95 | 140 / 155 | 230 / 255 | 460 / 505 | 520 | 740 / 750 |
| Lightning Impulse (BIL Full Wave, kV) | 125 | 200 | 325 | 550 | 1050 | 1425 | 1675 |
| Chopped Wave Lightning Impulse (kV) | 138 | 220 | 358 | 605 | 1155 | 1568 | 1843 |
| Switching Impulse Withstand (SIL, kV) | — | — | — | — | 850 | 1050 | 1300 |
| Rated Current Ir (A) | 630 / 1250 / 2000 / 3150 / 4000 / 5000 (Draw-lead or Draw-rod) | ||||||
| Dielectric Dissipation Factor tanδ | ≤ 0.005 (≤ 0.5%, typical 0.30% - 0.40% at 20°C) | ||||||
| Partial Discharge at 1.2 Um/√3 (pC) | ≤ 5 pC (Routine Factory Test Standard; IEC limit ≤ 10 pC) | ||||||
| Minimum Nominal Creepage Distance | ≥ 31 mm/kV (Heavy / Very Heavy anti-pollution sheds) | ||||||
| Cantilever Bending Load (N) | 1,250 N - 5,000 N (per voltage class and mechanical specification) | ||||||
| Short-Time Withstand Current | 25 × rated current for 2 s (thermally guaranteed) | ||||||
| Rated Frequency (Hz) | 50 / 60 Hz | ||||||
Higher insulation levels (e.g. 155/325 kV, 255/550 kV) and custom creepage distances are manufactured per transformer maker drawings.
Product Advantages & Engineering Highlights
Integrated Smart Online Monitoring Option: All 72.5kV to 550kV condenser bushings feature precision capacitive test taps compatible with real-time continuous Tan Delta & capacitance sensors.
Elimination of Bushing Fire & Explosion Hazards: According to CIGRE A2.37 and INMR field failure statistics, 48.7% of catastrophic transformer fires are initiated by aging oil-impregnated paper (OIP) bushing failures. ZLVOLT dry RIP and RIF condenser cores contain zero dielectric oil, eliminating bushing-initiated fire and explosion hazards, oil leakage, and routine oil maintenance over a 30+ year design life.
Alternative Ester Fluid (FR3 / MIDEL) Compatibility: Fully qualified for synthetic and natural ester dielectric liquids (Cargill Envirotemp FR3 and Shell MIDEL 7131) up to 500 kV. Furnished with high-temperature Viton™ (FKM) fluorocarbon elastomer seals per modern utility green-substation requirements.
Solid Dry RIP/RIF Condenser Core: 100% oil-free and gas-free construction with void-free dielectric layering.
CNC Closed-Loop Servo Winding: Tension uniformity controlled within ±2 N with robotic foil alignment (±0.1 mm) ensures void-free dielectric layering, maintaining partial discharge ≤ 5 pC at 1.2 Um/√3 and tan δ ≤ 0.35% at 20°C.
IEEE 693 High Seismic Compliance: Reinforced fiberglass composite core and heavy-duty flange casting qualified for 0.5g / 1.0g peak ground acceleration and severe cantilever bending moments.
Extreme Temperature Performance (-50°C to +55°C): Dual fluorosilicone O-rings and cryogenic-resistant resin matrix prevent seal embrittlement in Arctic climates and high-altitude mountain substations.
Hydrophobic HTV Silicone Housing: Direct vulcanization with chemical silane coupling bonding delivers persistent hydrophobicity transfer under severe coastal salt fog, desert sand, and industrial pollution (Class IV / Class E, ≥31 mm/kV).
Smart Condition Monitoring Ready: Standard precision capacitive test tap connects directly to Doble, OMICRON, and Qualitrol online diagnostic systems for continuous C1/C2 tan δ tracking and DFR frequency domain spectroscopy.
1-to-1 Retrofit Compatibility: Customized mounting flange PCD, oil-side CT pocket length, and draw-lead/draw-rod interfaces allow direct dimensional replacement of legacy OIP bushings from ABB, Siemens, Trench, or Micafil.
Suitable Service Conditions
Installation Angle: Any angle.
Environment: Indoor and outdoor; severe pollution, high humidity, severe cold and high-altitude (above 2000 m) versions available by agreement.
Ordering Information
When placing an order, please specify:
1. Electrical Parameters: Rated voltage, rated current, frequency, creepage distance class, oil-side length, draw-lead length (critical), CT mounting position length (critical).
2. Environmental Parameters: Ambient temperature range, pollution level, altitude.
3. Interfaces: Flange drawing of the transformer, terminal type, whether a test tap / voltage tap is required.
Note: Flange and terminal dimensions can be custom-designed to the transformer maker's drawings. Direct replacement engineering for existing installations is available.
Engineering & Selection Guides
Explore technical documentation and engineering selection guides relevant to oil-air transformer bushings:
- Prepare a Project Inquiry: Transformer Bushing RFQ Specification Guide
- Review Quality & Evidence: Factory Acceptance, Type Test Reports & Test Hall Facilities
- Insulation Comparison: RIP vs. RIF Dry-Type Bushings Technical Guide
- Test Evidence: Bushing Type Tests vs Routine Tests — Does the Report Cover Your Bushing?
- Diagnostic Testing: How to Compare Bushing Capacitance & Tan Delta Records
- Selection Guide: Transformer Bushing Interfaces, Ratings & Derating Guide
Reference Projects
Projects Using Oil-Air Transformer Bushings
550kV Bushings for the Zhongmei Yongcheng 2×1000MW Ultra-Supercritical Power Unit
550kV RIP Transformer Bushing (EBRGL-550/630) · 3 sets
363kV Bushings in Bulk for Huaneng Qingyang Wind-Solar Hybrid Demonstration (Lot A2)
363kV RIP Transformer Bushing (FBRGL-363/800) · 42 units
330kV Class Bushings for the 2GW Guoneng Ningdong Integrated Energy PV Base (No.2 Booster Station)
363kV RIP Transformer Bushing (EBRGL-363/800) · 24 units
252kV Bushings for the Huaneng Gongzhuling 235MW/470MWh Grid-Scale Storage Station
252kV RIP Transformer Bushing (FBRGL-252/630) · 3 sets
Product Recommendations
Explore Other Bushing Models
Model selection support
Need help with RIP/RIF Oil-Air Transformer Bushing?
Send your voltage, current and application — Daniel Yuan will reply by email.
Thank you! We'll reply to you by email.