Products
RIP/RIF High Current Bushing
EBRG Series | 24kV - 40.5kV | 4,000A - 31,500A (up to 40,000A custom)
Application
Technical drawing — dimensions and interfaces can be customized to your transformer flange.
Main Technical Index
| Main Technical Index (per IEC 60137 / GB/T 4109 / Patent ZL 2016 1 0001471.3) | |||
|---|---|---|---|
| Rated Equipment Voltage Um (kV) | 24 | 36 (Export Standard) | 40.5 |
| Power Frequency Withstand, 1 min (kV) | 61 / 65 | 80 | 95 |
| Lightning Impulse Withstand (BIL, kV) | 125 / 150 | 170 | 200 |
| Rated Current Ir (A) | 4,000 / 6,300 / 10,000 / 12,500 / 16,000 / 20,000 / 25,000 / 31,500 A (up to 40,000A custom; CTQC ZJ-26.0046 tested at 25,000 A) | ||
| Dielectric Dissipation Factor tanδ | ≤ 0.005 (≤ 0.5%) | ||
| Partial Discharge (pC) | ≤ 5 pC (Routine Factory Test Standard) | ||
| Cantilever Bending Load (N) | ≥ 3,150 N - 5,000 N (heavy copper conductor structural support) | ||
| Conductor Core Technology | Solid high-conductivity electrolytic copper rod / tubular bus with forced air/oil internal channel options | ||
Product Advantages & Engineering Highlights
Up to 31,500A Standard Rating (40,000A Custom, CTQC Tested to 25,000A): Industry-leading heavy-current dry-type condenser structure protected by Chinese Invention Patent ZL 2016 1 0001471.3.
Internal Convection & Skin-Effect Optimization: Hollow high-conductivity electrolytic copper conductors with convective thermal channels limit winding temperature rise to < 40 K even at continuous multi-kiloampere loads.
Slotted Eddy-Current Barrier Flange: Non-magnetic flange casting with patented circumferential de-looping slots breaks circular magnetic flux paths, reducing stray magnetic losses by up to 65%.
Export-Proven Heavy-Duty Reliability: 36kV / 12,000A units supplied to Toshiba Transformers Russia operating continuously in generator step-up service since 2014.
Custom Terminal Terminations: Multi-palm silver-plated flag terminals, threaded stud bars, and water/forced-oil cooling interfaces engineered precisely to transformer maker busbar specifications.
Typical Applications
- Generator step-up transformer low-voltage side
- Furnace transformers and rectifier transformers
- Electrolysis, steel and heavy industrial power supplies
Ordering Information
Please specify rated voltage and current, terminal type and hole pattern, flange drawing, oil-side/air-side lengths and ambient temperature. Thermal calculation sheets are available for continuous currents above 10kA.
Engineering & Selection Guides
Technical resources and selection guides for high-current generator and furnace bushings:
- Testing Guide: Bushing Type Tests vs. Routine Acceptance Tests Guide
- Selection Guide: Transformer Bushing Interfaces, Ratings & Derating Guide
- Prepare a Project Inquiry: Transformer Bushing RFQ Specification Guide
- Review Quality & Evidence: Factory Acceptance, Type Test Reports & Test Hall Facilities
Reference Projects
Projects Using High Current Bushings
40.5kV High-Current Bushings for the Zhangji Coal Mine Central 110kV Substation Retrofit
40.5kV Transformer Bushing (FBRG-40.5/5000) · 3 sets
Export to Russia: Bushings for Toshiba Transformers Russia
36kV Transformer Bushing (FBRG-36kV/12000A) · 3 units
126kV Bushings for the Zhundong Development Zone 220kV Transmission Project
126kV Transformer Bushing (FBRGL-126/630) + 40.5kV High-Current (FBRG-40.5/4000) · 8 units
252kV Bushings for the Huaneng Zuoquan Wind-Solar-Hydro-Storage-Hydrogen Multi-Energy Base
252kV Transformer Bushing (FBRGL-252/1250) + 24kV High-Current (FBRG-24/4000) · 10 units
Product Recommendations
Explore Other Bushing Models
Model selection support
Need help with RIP/RIF High Current Bushing?
Send your voltage, current and application — Daniel Yuan will reply by email.
Thank you! We'll reply to you by email.