RIP/RIF GIS Bushing
FGRG / EGRG Series | 72.5kV - 550kV | 630A - 5000A
Application
Technical drawing — dimensions and interfaces can be customized to your transformer flange.
Main Technical Index
| Main Technical Index (per IEC 60137 / GB/T 4109 / Q/ZL-JS-502-2026) | ||||||
|---|---|---|---|---|---|---|
| Rated Equipment Voltage Um (kV) | 72.5 | 126 | 145 / 170 | 252 | 363 | 550 |
| Power Frequency Withstand, 1 min (kV) | 140 | 230 | 275 / 325 | 460 | 520 | 740 |
| Lightning Impulse Withstand (BIL, kV) | 325 | 550 | 650 / 750 | 1050 | 1425 | 1675 |
| Switching Impulse Withstand (SIL, kV) | — | — | — | 850 | 1050 | 1300 |
| Rated Current (A) | 630 / 1250 / 2000 / 3150 / 4000 / 5000 (up to 8000A per project drawing) | |||||
| Dielectric Dissipation Factor tanδ | ≤ 0.005 (≤ 0.5%, typical 0.30% - 0.40% at 20°C) | |||||
| Partial Discharge at 1.2 Um/√3 (pC) | ≤ 5 pC (Routine Factory Test Standard) | |||||
| SF6 Operating / Proof Pressure | Rated 0.45 - 0.60 MPa / Proof Pressure 0.80 MPa | |||||
| Minimum Nominal Creepage Distance | ≥ 31 mm/kV (Class IV Heavy / Class E Very Heavy Pollution) | |||||
| Cantilever Bending Load (N) | ≥ 3,750 N - 12,500 N (per mechanical class & conductor diameter) | |||||
| Corona Grading Shield Ring | Integrated for 252kV and above; optional for 126kV and below | |||||
Note: 40.5kV compact GIS bays (PF 95kV / BIL 200kV) available on request. SF6-side interface dimensions (flange diameter, seal groove PCD, gas-side length) are custom-machined per switchgear maker drawings.
Product Advantages & Engineering Highlights
EHV Heavy-Current Performance (Up to 550kV / 5000A): Field-proven in landmark projects including 363kV/5000A and 550kV/4000A substation installations alongside leading global GIS manufacturers.
Gas-Tight Hermetic Flange Sealing: High-precision machined seal faces with proof pressure rating up to 0.80 MPa, ensuring zero SF6 gas leakage at the switchgear interface.
Solid Dry RIP/RIF Dielectric Core: No internal oil or gas volume inside the bushing body, eliminating partial discharge degradation, oil sampling routines, and explosion risks.
Seismic & Extreme Altitude Resilience: High bending load capacity (≥3,750 N to 12,500 N) and IEEE 693 compliance; proven in rugged high-altitude sites (e.g., State Grid Shennongjia 363kV at 2,000+ m).
Optimized Corona & Field Grading Shields: Integrated toroid corona shields for 252kV, 363kV, and 550kV classes suppress surface electric field stress below 1.5 kV/mm in SF6 gas environments.
Typical Applications
- GIS outgoing bays connecting to overhead lines or air-insulated equipment, 72.5kV-550kV
- 330kV booster stations of gigawatt-scale wind and solar bases
- Urban and indoor substations where compact layout is required
Ordering Information
1. Electrical Parameters: Rated voltage, current, insulation levels, creepage class.
2. Mechanical Interfaces: GIS maker's interface drawing (critical), SF6-side length, air-side terminal and shed requirements, CT requirements.
3. Environment: Ambient temperature, altitude, seismic requirement.
Engineering Guide: Unsure whether your substation bay requires a gas-to-air GIS switchgear bushing or an enclosed oil-to-SF6 transition bushing? Read our GIS vs Oil-SF6 Bushings Interface Guide.
Engineering & Selection Guides
Technical resources and selection guides for GIS gas-to-air bushings:
- Interface Comparison: GIS Bushings vs. Oil-SF6 Bushings Interface Guide
- Prepare a Project Inquiry: Transformer Bushing RFQ Specification Guide
- Review Quality & Evidence: Factory Acceptance, Type Test Reports & Test Hall Facilities
- Selection Guide: Transformer Bushing Interfaces, Ratings & Derating Guide
Reference Projects
Projects Using GIS Bushings
550kV GIS Bushings for the Anhui Xinqiao Smart (Phase I) Baiyun Substation
550kV GIS Bushing (EGRG-550/4000) · 12 units
363kV GIS Bushings for the State Grid Shennongjia Substation, Hubei
363kV GIS Bushing (FGRG-363/3150) · 21 units
363kV GIS Bushings for the Wuwei Liangzhou 3GW PV Desert-Control Project (No.1 330kV Station)
363kV GIS Bushing (FGRG-363/5000) · 18 units
Product Recommendations
Explore Other Bushing Models
Model selection support
Need help with RIP/RIF GIS Bushing?
Send your voltage, current and application — Daniel Yuan will reply by email.
Thank you! We'll reply to you by email.