Products
RIP/RIF Wall Bushing
FCRG / ECRGL Series | 24kV - 550kV | 630A - 5000A
Application
Technical drawing — dimensions and interfaces can be customized to your transformer flange.
Main Technical Index
| Main Technical Index (per IEC 60137 / GB/T 4109 / Factory Standards) | |||||||
|---|---|---|---|---|---|---|---|
| Rated Equipment Voltage Um (kV) | 24 | 40.5 | 72.5 | 126 | 252 | 363 | 550 |
| Power Frequency Withstand, 1 min (kV) | 61 | 95 | 140 | 230 | 460 | 520 | 740 |
| Lightning Impulse Withstand (BIL, kV) | 125 | 200 | 325 | 550 | 1050 | 1425 | 1675 |
| Switching Impulse Withstand (SIL, kV) | — | — | — | — | 850 | 1050 | 1300 |
| Rated Current (A) | 630 / 1250 / 2000 / 3150 / 4000 / 5000 | ||||||
| Dielectric Dissipation Factor tanδ | ≤ 0.005 (≤ 0.5%, typical 0.30% - 0.40% at 20°C) | ||||||
| Partial Discharge at 1.2 Um/√3 (pC) | ≤ 5 pC (Routine Factory Test Standard) | ||||||
| Cantilever Bending Load (N) | ≥ 1,250 N - 5,000 N (per voltage class and mounting span) | ||||||
| Housing Structure | Outdoor: Hydrophobic HTV Composite Silicone or Porcelain; Indoor: Smooth or Shedded FRP/Porcelain | ||||||
| Mounting Configuration | Horizontal, vertical, or angled through-wall mounting plate with custom bolt PCD | ||||||
Note: Wall sleeve length, indoor/outdoor span, flange mounting diameter and terminal stud geometry are manufactured according to substation architectural wall drawings.
Product Advantages & Engineering Highlights
Heavy-Duty Mechanical Cantilever & Seismic Rigidity: Engineered with a reinforced central mounting collar and high-modulus FRP tube to withstand continuous horizontal bending moments from self-weight, terminal cable tension, and IEEE 693 seismic vibrations.
Eddy-Current Induction Loss Mitigation: Non-magnetic stainless steel or high-strength aluminum mounting flange inserts prevent closed circular eddy-current loops and localized induction heating in building concrete rebar.
Solid Dry Fire-Retardant & Hermetic Barrier: Solid RIP/RIF dry core with Class F thermal endurance acts as a natural flame-retardant and hermetic barrier between outdoor switchyards and indoor control halls; the oil-free, gas-free construction removes bushing oil-leakage risk by design.
Asymmetric Indoor/Outdoor Environment Adaptation: Custom shed profiles accommodate sharp temperature and pollution differentials between heated/air-conditioned indoor switchrooms and extreme outdoor ambient (-50°C to +55°C).
Proven EHV Performance: Up to 252kV/2000A in continuous service — including 18 units delivered to Tatneft, Russia, operating reliably since 2016.
Online Measurement & Diagnostic Tap: Factory-installed capacitive test tap facilitates continuous insulation monitoring and power-frequency capacitance / tan δ verification.
Typical Applications
- Power station and substation wall penetrations, 24kV-252kV
- Industrial plants: steel, coal, chemical, oil & gas
- Railway traction power supply buildings
Ordering Information
Please specify rated voltage and current, wall thickness and opening drawing, indoor/outdoor side lengths, creepage class and whether a voltage tap is required.
Engineering & Selection Guides
Technical resources and selection guides for high-voltage wall bushings:
Reference Projects
Projects Using Wall Bushings
Product Recommendations
Explore Other Bushing Models
Model selection support
Need help with RIP/RIF Wall Bushing?
Send your voltage, current and application — Daniel Yuan will reply by email.