Products
RIP/RIF Oil-SF6 Bushing
YQRGL Series | 40.5kV - 550kV | 630A - 4000A
Technical drawing — dimensions and interfaces can be customized to your transformer flange.
Main Technical Index
| Main Technical Index (per IEC 60137 / GB/T 4109 / Q/ZL-JS-502-2026) | ||||||
|---|---|---|---|---|---|---|
| Rated Equipment Voltage Um (kV) | 40.5 | 72.5 | 126 | 252 | 363 | 550 |
| Power Frequency Withstand, 1 min (kV) | 95 | 140 | 230 | 460 | 520 | 740 |
| Lightning Impulse Withstand (BIL, kV) | 200 | 325 | 550 | 1050 | 1425 | 1675 |
| Switching Impulse Withstand (SIL, kV) | — | — | — | 850 | 1050 | 1300 |
| Rated Current Ir (A) | 630 / 1250 / 2000 / 2500 / 3150 / 4000 | |||||
| Dielectric Dissipation Factor tanδ | ≤ 0.004 (≤ 0.40%, typical 0.30% at 20°C) | |||||
| Partial Discharge at 1.2 Um/√3 (pC) | ≤ 5 pC (Routine Factory Test Standard) | |||||
| SF6 Operating / Proof Pressure | Rated 0.45 - 0.60 MPa / Proof Test 0.80 MPa | |||||
| Cantilever Bending Load (N) | ≥ 3150 / 4000 / 5000 N per mechanical class | |||||
Product Advantages & Engineering Highlights
Direct Enclosed Transition: Connects transformer oil directly to SF6 switchgear busducts in a single hermetically sealed, dry-type capacitive core — eliminating open-air bushings and substation clearance constraints.
Hermetic Dual-Stage Barrier with Sniffer Port: Dual-groove fluorosilicone seals with an intermediate test chamber prevent SF6 cross-contamination into transformer oil and vice versa, tested to a helium leak rate < 1 × 10−6 mbar·l/s.
Eco-Gas (C4F7N / Clean Air) Ready: Solid resin core and field grading screens are fully compatible with both conventional SF6 gas and emerging eco-efficient gas mixtures (C4F7N / synthetic dry air).
Full EHV Coverage (40.5kV to 550kV): Accommodates rated currents up to 4000A with proof test pressure of 0.80 MPa on the gas side.
Solid RIP/RIF Explosion-Proof Core: 100% dry, cured insulation contains zero pressurized oil or gas inside the core body, eliminating fire hazards and oil-level maintenance.
1-to-1 Retrofit Compatibility: Tailor-machined mounting collars and CT pocket extensions allow drop-in replacement of aging OIP oil-SF6 bushings without modifying existing GIS gas compartments.
Typical Applications
- Transformer-to-GIS/GIL direct enclosed connections from 40.5kV to 550kV
- Compact indoor and underground substations requiring complete elimination of open air bushings
- Thermal and hydro power station generator step-up (GSU) transformer connections to GIS busducts
- Retrofit replacement of aging oil-paper insulated (OIP) oil-SF6 transition bushings
Ordering Information
Please specify rated voltage and current, insulation levels, both-side flange drawings, SF6-side and oil-side lengths, CT requirements and ambient conditions.
Engineering Guide: For detailed flange geometry, CT pocket verification, and media boundary comparisons between YQRGL oil-to-SF6 bushings and FGRGL/EGRGL gas-to-air GIS bushings, consult our GIS vs Oil-SF6 Bushings Interface Guide.
Engineering & Selection Guides
Technical resources and selection guides for transformer-to-GIS oil-SF6 bushings:
- Interface Comparison: GIS Bushings vs. Oil-SF6 Bushings Interface Guide
- Prepare a Project Inquiry: Transformer Bushing RFQ Specification Guide
- Review Quality & Evidence: Factory Acceptance, Type Test Reports & Test Hall Facilities
- Selection Guide: Transformer Bushing Interfaces, Ratings & Derating Guide
Product Recommendations
Explore Other Bushing Models
Model selection support
Need help with RIP/RIF Oil-SF6 Bushing?
Send your voltage, current and application — Daniel Yuan will reply by email.
Thank you! We'll reply to you by email.